Skip to content
English
  • There are no suggestions because the search field is empty.

Wireless Network Confirmation: A Modbus Polling Tool Tutorial

Discover how to verify the functionality of your wireless network with a Modbus polling tool. This article provides a step-by-step guide for network confirmation.

Is your wireless network operating effectively? This tutorial demonstrates the use of a Modbus polling tool to confirm the health and reliability of your network. Ensure your heat trace system operates smoothly with this practical guide.

Resources

Rad900 User Manual Download

PSI Configuration Download Page

Scroll down to "Downloads" and then to "Software"

Modbus Poll Software Download

USB to RS-485 Converter that we use

Typical Modbus Configurations

Note that the below are standard Modbus communication parameter setups. Some heat trace controllers have the ability to modify this but these are normally what they are.

Manufacture

Controller Type

Protocol Option

Serial Setup (Baud Rate, Data Bits, Parity, Stop Bits)

nVent (Digitrace, Raychem) 920 Modbus RTU (serial)
Modbus TCP (Ethernet)
9600,8,N,2
nVent (Digitrace, Raychem) 910 Modbus RTU (serial)
Modbus TCP (Ethernet)
9600,8,N,2
nVent (Digitrace, Raychem) NGC30 Modbus RTU (serial)
Modbus TCP (Ethernet)
9600,8,N,2
nVent (Digitrace, Raychem) NGC40 Modbus RTU (serial)
Modbus TCP (Ethernet)
9600,8,N,2
nVent (Digitrace, Raychem) T2000 Modbus RTU (serial)
Modbus TCP (Ethernet)
9600,8,N,2
nVent (Digitrace, Raychem) Elexant 4010i Modbus RTU (serial)
Modbus TCP (Ethernet)
9600,8,N,1
Thermon TC202/201/102/101 Modbus ASCII 9600,7,N,2
Thermon TCM2 Modbus RTU 9600,8,N,1
Thermon  TC1818a Modbus ASCII
Modbus RTD
9600,7,N,2
9600,8,N,1
Thermon  TCM18 Modbus ASCII
Modbus RTD
9600,7,N,2
9600,8,N,1

Modbus Polling Registers for Testing

Manufacture

Controller Type

Modbus Address Function Code Register Value
nVent (Digitrace, Raychem) 920 Set on controller 3 1  
nVent (Digitrace, Raychem) 910 Set on controller 3 1  
nVent (Digitrace, Raychem) NGC30 Set on controller 3 1  
nVent (Digitrace, Raychem) NGC40 Set on controller 3 1  
nVent (Digitrace, Raychem) T2000 Set on controller 3 1  
nVent (Digitrace, Raychem) Elexant 4010i Set on controller 3 1  
Thermon TC202/201/102/101 Set on controller 3 103 Maintaint Temp CCT1
Thermon TCM2 Set on controller 3 2 Maintaint Temp CCT1
Thermon  TC1818a Set on controller 3 103 Maintaint Temp CCT1
Thermon  TCM18 Set on controller 3 366 Maintaint Temp CCT1

nVent 920 Controllers utilize a Modbus address and a Sub Address.

Sub address 0 (zero), you will use the register number mentioned above. For every subaddress 512 is to be added to the register. Sub Address 0 = Register+0, Sub Address 1 = Register+512, Address 2 = Register+(512*2), 

Depending on what Modbus Polling tool you use an offset of 1 may be required for the register number. Ex. If you aren't haveing luck increase the register number by 1.

Whenever polling an ACSII controller ensure the quantity of data bits your polling is always 1 bit.