nVent 920 Controller Settings and Programming

This Page Covers the nVent 920 Controller's Programming and Settings in Great Depth.

Introduction

In this article, we'll delve into the intricacies of the nVent 920 Controller, exploring its settings, programming capabilities, and the myriad ways it enhances operational efficiency. From configuring alarms to fine-tuning control parameters, we'll leave no stone unturned as we uncover the full potential of this versatile device.

Whether you're a seasoned professional seeking to optimize your heat management system or a newcomer looking to harness the power of cutting-edge technology, this article is your definitive guide to unlocking the capabilities of the nVent 920 Controller. Join us as we embark on a journey to explore the fascinating world of industrial heat management.

Resources:

Digitrace 920 Operator Console Manual

Raychem-IM-H56874-920series

 

920 Series HTC CONFIGURATION SHEET V3.11 TO V3.14

Configuration Mode Main Menu Other Alarms Configuration Sub-Menu
Parameter Factory Parameter Factory
Control Setpoint 68°F (20C) Lo Load Enable
Lo TS 1 14°F (-10C) Lo Load 1.0 A
Lo Load 1.0A Lo Load Filter 0 sec
Hi GFI 50 mA Hi Load Disable
GFI Trip 75 mA Hi Load *n/a (30.0A)
    Hi Load Filter *n/a (0 sec)
TS Alarms Configuration Sub-Menu Hi GFI Enable
Parameter Factory Hi GFI 50 mA
TS 1 Fail Enable Hi GFI Filter 0 sec
Lo TS 1 Enable GFI Trip Enable
Lo TS 1 14°F (-10C) GFI Trip 75 mA
Hi TS 1 Disable Lo Volt Enable
Hi TS 1 *n/a(212°F(100°C)) Lo Volt 90 V
TS 2 Fail Disable Lo Volt Filter 0 sec
Lo TS 2 Disable Hi Volt Disable
Lo TS 2 *n/a (14°F(-10°℃)) Hi Volt *n/a (270 V)
Hi TS 2 Disable Hi Volt Filter *n/a (0 sec)
Hi TS 2 *n/a (212°F(100℃)) Lo Resist Disable
Lo TS Filter 0 min Lo Resist *n/a (50%)
Hi TS Filter *n/a (0 min) Lo Resist Filter *n/a (0 sec)
Latch TS Alarms Yes Hi Resist Disable
TS CTL Fail Enable Hi Resist *n/a (50%)
    Hi Resist Filter *n/a (0 sec)
    Nominal Resist *n/a (6.00 (2)
    Overcurrent Trip Enable
    Switch Fail Enable
    HTC Reset Disable
    C.B. Limiting Disable
    Power Limiting Disable
    Switch Limiting Disable
    Contactor Count *n/a (Enable)
    Contactor Count *n/a (200,000)
    EEROM Data Fail Enable
                       Point Setup Sub-Menu Common Setup Sub-Menu  
Parameter Factory Parameter Factory  
Tag TAG-(factory ID) Temp. Units °F  
Switch Control Mode Proportional Version V3.1x  
Prop Band 4°F (2°C) Ext. Input Not Used  
Deadband *n/a (5°F(3C)) Ext. Output Not Used  
Cycle Time *n/a (10 min) Flash Alarm Output Yes  
Switch Rating 30.0 A Alarm Output N.C.  
Circuit Breaker 30.0 A Language English  
Max Power 7200 W Point B Used Yes  
3 Ph Pwr Calc No Passcode 0  
TS Fail Mode Off Scroll Delay 0.15 secs  
TS CTL Mode TS1-Fail Off Copy Config ... (see user manual)  
TS 1 Type 100Ω Plat      
TS 1 Lead Resist *n/a (0 (2) Communication Setup Sub-Menu  
TS 1 Hi Limit Disable Parameter Factory  
TS 2 Type 1000 Plat Protocol HTCBUS  
TS 2 Lead Resist *n/a (0 Ω) HTCBUS Addr (factory ID)  
TS 2 Hi Limit Disable Modbus Addr *n/a (1)  
Volt Source Pt. A (or Pt. B) Modbus Sub Addr *n/a (0)  
Fixed Volt *n/a (120V) Baud Rate AUTO  
Volt Turns Ratio 1.00 to 1 Parity *n/a (None)  
Current Turns Ratio 1.00 to 1 Hardware None, Modem, RS-232, RS-485  
Auto-cycle Enable Driver Auto  
Auto-cycle Interval 8 Profile Auto  
Auto-cycle Units Hours Tx Delay 0.06 secs  
Override Source Remote *n/a: Parameter may only appear if certain features are enabled. Values shown in brackets are the Factory defaults if the settings are enabled
Load Shedding Disable